The Model FL3100H is an Ultraviolet
/ Infrared flame detector designed to detect fires and provide
alarm outputs directly from the detector while maintaining false
alarm immunity. It detects fires by monitoring in both the ultraviolet
(UV) and infrared (IR) spectral ranges, making it highly immune
to false alarms. Configurations with dual Modbus and HART are available. Modbus and HART data can be used for predictive maintenance.
FL3100 Series flame detectors' electronics are integral within
their explosion-proof housings, allowing detector information
to be processed at the point of detection. The detectors also
provide a 4-20 mA stepped output signal indicating detector status.
The COPM (Continuous Optical Path Monitoring) self-test feature
checks the optical path integrity (window cleanliness) and the
detectors' electronic circuitry once every minute. CSA, FM, IECEx, ATEX approved. SIL 3 suitable. FM certified to IEC 61508.
FL3100H
FEATURES AND BENEFITS
Wide field of view
Greater fire
detection coverage
4-20 mA
stepped output
Industry
standard for remote alarm and fault indication
HART and dual Modbus communication available
Provides complete status and control capability in the control room
Wide operating
temperature range
Permits operation at higher ambient temperature
Continuous
Optical Path Monitoring (COPM)
Checks optical path integrity
and detector's electronic circuitry once every minute
Three SPDT
high current programmable relay outputs
Immediate
and time delayed relay outputs for alarm, programmable
relay outputs